Monitor Temperature in Cold Storage Area with Sensaphone FGD-0107 Sensor NIST Certification included on this sensor
Glass bead filled vial buffers any momentary fluctuations that may cause a preliminary alarm dial out, such as defrost cycles, opening of doors, and fans circulating air. Glass beads slow the response time of the sensor allowing normal daily operations to occur without having an alarm.
Temperature Sensor FGD-0107 Specifications:
Must be used with a Sensaphone.
Accurate to ± 1°C (± 1.8°F)
Compatible with Sensaphone models: 400, 800, 1400, 1800, 2800, 2000, StationSitter, Express II, and WEB600.
Temperature Range: Differs depending on Sensaphone models:
400, 800: -20° to 150°F (-30° to 65°C)
1400, 1800, 2800: -109° to 115°F (-78° to 46°C)
2000: -121° to 123°F (-85° to 51°C)
Express II: -85° to 200°F (-65° to 93°C)
Package Contents: (1) Temperature sensor, (1) 12’ wire and Installation instructions.
Temperature sensor FGD-0107 was designed for
cold storage temperature monitoring inside freezers and
refrigerators. Glass bead filled vial buffers any momentary fluctuations
that may cause a preliminary alarm, such as defrost cycles, door openings and fans circulating air. The temperature seen by the
Sensaphone is closer to the actual temperature of the items in the
cooler than the air temperature. The glass beads slow the response time
of the sensor allowing normal daily operations to occur without having
an alarm initiated.
A popular combination is to use this sensor
with the new Web600 for a low cost cold storage solution that is web based and capable of monitoring ultra low temperature applications down
to -85 Deg C.